DC cable size and voltage drop calculator

Low-voltage DC carries large currents, so the cable size matters. Enter the voltage, the power or current and the length to get a cable size, the voltage drop and the power lost as heat.

DC cable calculator

Use the one-way length: the distance from the battery or panels to the inverter or controller, not the total of both wires.

Battery voltage, or the string's working voltage (Vmp × panels in series)
Or enter the current below
–amps
–mm² minimum
–mm² cable
–% drop

Cable sizes are checked for voltage drop and for a typical current rating in free air with 25% margin. Battery cables also need a fuse or breaker sized to the cable, and the installation must comply with SANS 10142-1.

A rough guide for planning, not a quote. An installer confirms sizes and prices after seeing your bill, roof and distribution board.

Power is volts × amps, so the same 3 000 W is 250 A at 12 V but only about 60 A at 48 V. Thin cable on a big current wastes power as heat, makes the inverter see a low voltage and trip, and in the worst case melts. That is why battery cables are short and thick, and why solar panels are wired in series to raise the voltage.

How the calculator works

  • Current: watts ÷ volts, or the current you enter.
  • Minimum size: 2 × one-way length × current × 0.0195 ÷ (voltage × allowed drop). 0.0195 Ω·mm²/m is copper at about 50 °C, a warm battery room or roof.
  • Cable size: the smallest standard size that meets the voltage drop and carries 125% of the current.
  • Loss: voltage drop × current, in watts.

Common rules of thumb

RunTypical dropTypical cable
48 V lithium battery to a 5 kW inverter, 2 munder 2%35 mm²
Solar string, 400 V, 10 A, 25 munder 1%4 or 6 mm² PV cable
12 V battery to a 1 kW inverter, 1.5 munder 2%25–35 mm²
12 V garden light, 2 A, 15 munder 5%2.5 mm²

Inverter manuals give the battery cable size and fuse to use; follow them when they ask for more than this calculator.

Use the right cable

Panel strings need UV-resistant, double-insulated solar cable (often labelled H1Z2Z2-K or PV1-F), with MC4 connectors of the same make. Battery runs use fine-stranded flexible cable with crimped lugs, not house wire. AC wiring from the inverter to the distribution board, earthing and surge protection are signed off by a registered electrician on the Certificate of Compliance; see solar installation.

Frequently asked questions

What size cable do I need from a 48 V battery to a 5 kW inverter?
About 105 A at full load; most installers use 35 mm² for runs of 1 to 3 m, with a fuse or DC breaker of about 125 to 160 A. Check the inverter manual.
Why is my inverter showing a low battery voltage under load?
Often the battery cable is too thin or too long, or a lug is loose. The voltage drop under load makes the inverter think the battery is flat. Shorter, thicker cable and tight crimped lugs fix it.
What size PV cable do I need for solar panels?
For home strings of 8 to 13 A, 4 mm² solar cable is standard, and 6 mm² for long runs over about 30 m.
Can I use this for AC cable?
No. AC circuits from the inverter to the distribution board are sized under SANS 10142-1 by an electrician, taking the breaker, installation method and grouping into account.

Get free solar quotes

Tell us what you need and where. An installer or supplier who works in your area quotes you directly. Free, no obligation.

Size it roughly (optional)

Tick what must keep running when the power is off. The estimate goes into your request so installers can quote closer to what you need.

Hours of backup
Sun where you are

5.0 kWh per kWp a day

–kVA inverter
–kWh battery
–kWp panels

Tick a few loads or enter your monthly units to see a size.

A rough guide only. An installer confirms the size after looking at your bill, roof and distribution board.

Tick what applies (optional)

Free and no obligation. By sending you agree that we may share your request with a suitable installer or supplier. See our privacy policy.

Get free solar quotes