DC cable size and voltage drop calculator
Low-voltage DC carries large currents, so the cable size matters. Enter the voltage, the power or current and the length to get a cable size, the voltage drop and the power lost as heat.
DC cable calculator
Use the one-way length: the distance from the battery or panels to the inverter or controller, not the total of both wires.
Cable sizes are checked for voltage drop and for a typical current rating in free air with 25% margin. Battery cables also need a fuse or breaker sized to the cable, and the installation must comply with SANS 10142-1.
A rough guide for planning, not a quote. An installer confirms sizes and prices after seeing your bill, roof and distribution board.
Power is volts × amps, so the same 3 000 W is 250 A at 12 V but only about 60 A at 48 V. Thin cable on a big current wastes power as heat, makes the inverter see a low voltage and trip, and in the worst case melts. That is why battery cables are short and thick, and why solar panels are wired in series to raise the voltage.
How the calculator works
- Current: watts ÷ volts, or the current you enter.
- Minimum size: 2 × one-way length × current × 0.0195 ÷ (voltage × allowed drop). 0.0195 Ω·mm²/m is copper at about 50 °C, a warm battery room or roof.
- Cable size: the smallest standard size that meets the voltage drop and carries 125% of the current.
- Loss: voltage drop × current, in watts.
Common rules of thumb
| Run | Typical drop | Typical cable |
|---|---|---|
| 48 V lithium battery to a 5 kW inverter, 2 m | under 2% | 35 mm² |
| Solar string, 400 V, 10 A, 25 m | under 1% | 4 or 6 mm² PV cable |
| 12 V battery to a 1 kW inverter, 1.5 m | under 2% | 25–35 mm² |
| 12 V garden light, 2 A, 15 m | under 5% | 2.5 mm² |
Inverter manuals give the battery cable size and fuse to use; follow them when they ask for more than this calculator.
Use the right cable
Panel strings need UV-resistant, double-insulated solar cable (often labelled H1Z2Z2-K or PV1-F), with MC4 connectors of the same make. Battery runs use fine-stranded flexible cable with crimped lugs, not house wire. AC wiring from the inverter to the distribution board, earthing and surge protection are signed off by a registered electrician on the Certificate of Compliance; see solar installation.
Frequently asked questions
What size cable do I need from a 48 V battery to a 5 kW inverter?
Why is my inverter showing a low battery voltage under load?
What size PV cable do I need for solar panels?
Can I use this for AC cable?
Get free solar quotes
Tell us what you need and where. An installer or supplier who works in your area quotes you directly. Free, no obligation.
Size it roughly (optional)
Tick what must keep running when the power is off. The estimate goes into your request so installers can quote closer to what you need.
5.0 kWh per kWp a day
Tick a few loads or enter your monthly units to see a size.
A rough guide only. An installer confirms the size after looking at your bill, roof and distribution board.